4.5.3 Front panel control operaon
Press and hold the stop buon (Figure: Front panel controls, item 4) for 5 seconds to
stop the pump in Auto shut down mode (recommended). Repeat within 10 seconds to
stop the pump in the Fast shut down mode. The running LED (Figure: Front panel
controls, item 2) ashes while the pump is slowing down and will then turn o when the
pump has shut down.
4.6 Automac shut down
Normally, if an alarm condion exists, the control system will shut down the dry
pumping system. When the dry pumping system shuts down, all the purge gas valves
close and the pump stops. For the dry pumping systems containing a dry pump and
booster combinaon, some alarms will cause only the booster to stop, and not the full
dry pumping system.
Table 23
Alarm acons
Alarm descripon
Alarm stops the dry pump
Alarm stops the booster
pump
EMS or system conguraon fault Yes Yes
Exhaust pressure* Yes Yes
Booster stator temperature† No Yes
Dry pump stator temperature Yes Yes
Booster status† No Yes
Dry pump status Yes Yes
* Not applicable to systems with light
‑
duty gas module.
† Not applicable to systems which do not contain a booster.
4.7 Unplanned shut down and alarms
The dry pumping system is ed with a number of pump protecon sensors that will
give warnings and alarms. Refer to Table: Pump protecon sensors.
Table 24
Pump protecon sensors
Sensor
Warning condion
triggered
Alarm condion
triggered
Exhaust pressure transducer* 0.3 barg (4.4 psig) 0.4 barg (5.8 psig)
DP TEMP temperature
GXS160 and GXS160/1750 150 °C 160 °C
GXS250 and GXS250/2600 150 °C 165 °C
All GXS450 dry pumping systems 170 °C 180 °C
All GXS750 dry pumping systems 180 °C 190 °C
MB stator temperature 120 °C 130 °C
* Not available on the dry pumping systems with the light
‑
duty gas module.
Page 61
M58800880_H - Operaon