EasyManua.ls Logo

Fluke DSX-8000 - Page 202

Fluke DSX-8000
700 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Versiv Series Cabling Certification Product Family
Technical Reference Handbook
166
Notes
Set the reference only after the testers are at an
ambient temperature between 10 °C and 40 °C
(5F and 10F).
The tester will not let you set the reference if the
patch cord is longer than 30 cm (12 in).
You can also set the reference with a 50 patch
cord
3 On the home screen, select a coaxial cable test.
4 On the home screen, tap TOOLS, then tap Set Reference.
5 On the SET REFERENCE screen tap TEST.
GPU179.EPS
Figure 75. Reference Connections for Tests on Coaxial Cabling
DSX-CHA003
COAX ADAPTER
DSX-CHA003
COAX ADAPTER
Coaxial adapter
with F connector
adapter
30 cm (12 in) 75 
coaxial patch cord
Coaxial adapter
with F connector
adapter

Table of Contents

Related product manuals