Chapter 19: Custom Media and Test Limits
Change the NVP
571
Set the NVP to a Specified Value
Use this procedure to set the NVP to a specified value, such as the
value specified by the manufacturer. The NVP value applies to the
selected cable type.
Note
If you are on the NEW CUSTOM CABLE screen, tap
the NVP panel, then go to step 4 below.
To enter a specified NVP value
1 On the home screen, tap the test setup panel, tap a copper
test, then tap EDIT.
2 On the TEST SETUP screen, make sure that the Cable Type is
correct.
3 Under the Cable Type, tap NVP.
4 On the NVP screen, use or to change the NVP value.
5 Tap DONE, then tap SAVE.
Find a Cable's Actual NVP
To find a cable's actual NVP, you can use the NVP screen to adjust
the measured length to match a known length of cable. The NVP
value applies to the selected cable type.
To find a cable's NVP
Note
If you are on the NEW CUSTOM CABLE screen, tap
the NVP panel, then go to step 4 below.
1 On the home screen, tap the test setup panel, tap a copper
test, then tap EDIT.
2 On the TEST SETUP screen, make sure that the Cable Type is
correct.
-continued-