Chapter 9: Certify Fiber Cabling
Autotest in Far End Source Mode
287
Step 3: Do an Autotest in Far End Source Mode
WCaution
If you disconnected the test reference cord from the
output of the tester, you must set the reference
again to make sure your measurements are reliable.
3-1 On the SET REFERENCE, when the set reference or TRC
verification procedure is completed, tap NEXT to see how to
connect to the fiber under test.
3-2 Clean and inspect the all connectors.
3-3 Make the connections to do the test on the fiber, as shown on
the screen and in Figure 120, then press HOME.
3-4 If necessary, select End 1 or End 2: On the home screen, tap the
Next ID: panel, then tap the End 1/End 2 control to select an
end.
3-5 Tap TEST on the main tester or press on the main or
remote tester.
3-6 If the CHECK FIBER CONNECTIONS screen shows an open
fiber:
Make sure that all connections are good and no fibers
have damage. Use the VFL to make sure the fiber under
test has continuity.
If you are connected to a fiber at a patch panel, and you
are not sure you are connected to the correct fiber,
connect the main tester’s INPUT fiber to different
connections until the test continues.
3-7 If Auto Save is on, the tester uses the next ID to save the
results.
If Auto Save is off, the SAVE RESULT screen shows the next
ID available. You can change the ID if necessary.