Settings for Loss/Length Tests on Fiber
Table 11 gives descriptions of the settings for loss/length tests on
fiber. To set up a project, which includes the settings in Table 11,
cable IDs, and operator names, see Chapter 17.
To set up a loss/length test
1 On the home screen, tap the test setup panel.
2 On the CHANGE TEST screen, select a fiber test to change,
then tap EDIT.
Or to set up a new fiber test, tap NEW TEST. If no module is
installed, the MODULE screen shows. Tap the correct CertiFiber
Pro module.
3 On the TEST SETUP screen, tap the panels to change settings
for the test. See Table 11.
4 On the TEST SETUP screen, tap SAVE when your test setup is
completed.
5 On the CHANGE TEST screen, make sure the button next to
the test is selected, then tap USE SELECTED.
Loss/Length Settings for Limits that Calculate
a Loss Limit
Some test limits do not specify a limit for loss measurements. They
specify maximum values of loss per kilometer of fiber and for the
connectors and splices in the link. Then, the tester uses the
measured length of the link, the number of connectors in the
link, and the number of splices in the link to calculate a loss limit
for that link.
When you select such a limit, you must enter the number of
connectors and splices that are in the link. To enter these values,
tap Reference Method or No. of Connections/Splices on the TEST
SETUP screen. See No. of Connections/Splices in Table 11 on page
256.