EasyManua.ls Logo

Fluke DSX-8000 - About the EF-TRC (Encircled-Flux Test Reference Cords)

Fluke DSX-8000
700 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Versiv Series Cabling Certification Product Family
Technical Reference Handbook
248
About the EF-TRC (Encircled-Flux Test Reference Cords)
The CFP-MM and CFP-QUAD kits includes the EF-TRC (encircled
flux test reference cords), which have signal conditioners on the
cords. When you use the EF-TRCs with the CertiFiber Pro
multimode modules, your tester complies with IEC 61280-4-1, ISO/
IEC 14763-3, and TIA-526-14-B standards for encircled flux.
Measurements made with compliant equipment change less than
10 % for losses of 1 dB or more when you make them at different
times or with different equipment that is also compliant.
Note
The IEC 61280-4-1, ISO/IEC 14763-3, and
TIA-526-14-B standards require your optical loss
test set to comply with encircled flux standards at
850 nm with 50 µm/125 µm fiber. The standards
recommend compliance at 850 nm with 62.5 µm/
125 µm fiber and at 1300 nm with 50 µm/125 µm
and 62.5 µm/125 µm fiber.
WCaution
To prevent damage to fiber connectors, to prevent
data loss, and to make sure that your test results are
as accurate as possible:
Use the EF-TRC cords only with the CertiFiber Pro
modules or with sources approved by Fluke
Networks for use with the cords. If a source does
not have the correct LED and internal fibers, the
EF-TRC cords will not make launch conditions that
agree with encircled flux standards.
When you use the EF-TRCs, DO NOT use other
mandrels.
Always follow the handling guidelines given in
Figure 106.
Put protective caps on all connectors when you do
not use them.

Table of Contents

Related product manuals