EasyManua.ls Logo

Fluke DSX-8000 - Page 237

Fluke DSX-8000
700 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 6: Diagnose Copper Test Failures
The HDTDX Analyzer
201
GPU114.EPS
Figure 88. HDTDX Plot
The vertical scale shows the amplitudes of the crosstalk signals.
The numbers on the scale are for reference only and do not
have units. The values on the scale are related to the limits for
NEXT in the selected test limit. For example, a crosstalk signal
that goes to 20 on the scale when you use a Cat 5 limit goes to
over 40 when you use a Cat 6 limit.
The orange, dashed lines are at the start and end of the cabling
that the tester includes in the test results.
The horizontal scale shows the distance along the cabling.
B
D
A
E
G
F
C

Table of Contents

Related product manuals