5-66 750/760 Feeder Management Relay GE Multilin
5.6 S5 PROTECTION 5 SETPOINTS
5
d) OVERVOLTAGE
PATH: SETPOINTS ÖØ S5 PROTECTION ÖØ VOLTAGE ÖØ OVERVOLTAGE 1(2)
To protect voltage sensitive loads and circuits against sustained overvoltage conditions, the Overvoltage 1 and 2 protection
features can be used to either cause a trip or generate an alarm when the voltage exceeds a specified voltage value for a
specified time delay. The setpoints above are repeated for both Overvoltage 1 and Overvoltage 2.
Figure 5–30: OVERVOLTAGE LOGIC
îš„ OVERVOLTAGE 1
îš„ [ENTER] for more
OVERVOLTAGE 1
FUNCTION: Disabled
Range: Disabled, Trip, Alarm, Latched Alarm, Control
OVERVOLTAGE 1
RELAYS (3-7): -----
Range: Any combination of 3 to 7 Auxiliary relays
OVERVOLTAGE 1
PICKUP: 1.25 x VT
Range: 0.00 to 1.25 x VT in steps of 0.01
OVERVOLTAGE 1
DELAY: 2.0 s
Range: 0.0 to 6000.0 s in steps of 0.1
PHASES REQUIRED FOR
OPERATION: All Three
Range: Any One, Any Two, All Three
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
Courtesy of NationalSwitchgear.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Feeder Management Relay 750 and is the answer not in the manual?

GE Feeder Management Relay 750 Specifications

General IconGeneral
BrandGE
ModelFeeder Management Relay 750
CategoryProtection Device
LanguageEnglish

Related product manuals