Diagnostics > Status Configuration > Device Status
Diagnostics
RM GUI HiSecOS EAGLE20/30
Release
3.0
09/2015
421
Table
Parameters Meaning
Temperature Activates/deactivates the monitoring of the temperature in the device.
Possible values:
marked
(default setting)
Monitoring is active.
The "Device status" changes to "Error" if the temperature exceeds /
falls below the threshold values.
unmarked
Monitoring is inactive.
You specify the temperature thresholds in the
Basic Settings > System
dialog, in the "Temperature (°C)" field.
Connection error Activates/deactivates the monitoring of the link on the ports/interfaces.
Possible values:
marked
Monitoring is active.
The "Device status" changes to "Error" if the link interrupts on a
monitored port/interface.
In the "Port" tab, you have the option of selecting the ports/interfaces
to be monitored individually.
unmarked
(default setting)
Monitoring is inactive.
External memory
removal
Activates/deactivates the monitoring of the active external memory.
Possible values:
marked
Monitoring is active.
The "Device status" changes to "Error" if you remove the active
external memory from the device.
unmarked
(default setting)
Monitoring is inactive.
You specify the active external memory in the
Basic Settings >
Load/Save dialog, "External Memory" frame.