6 Building air conditioning controls
CSNET WEB (PSC-A160WEB1)
TCGB0106 rev.0 - 12/2014
443443
6
Export buttons
Save to le button writes in a selected comma-separated values le the content of the table.
Copy to clipboard button will set in your clipboard the content of the table, separating the information by tabs.
In both cases the information of the table is ready to create an easy view of the information and an easier exportation to
other programs like Excel.
Available data for Packaged
The available data for CSNET WEB for Packaged is:
Address
(Note 1)
Name Description Read/Write
0 EXIST
0: Not exist
1: Exist
Read
1 SYSTEM_ADDRESS
H-LINK 1: 0~15
H-LINK 2: 0~63
Read
2 UNIT_ADDRESS
3 SET_ONOFF
ON/OFF setting order:
0: Stop
1: Run
Read/Write
4 SET_MODE
Mode setting order:
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Read/Write
5 SET_FAN
Fan setting order:
0: Low
1: Medium
2: High
Read/Write
6 SET_TSET
Setting temperature
17ºC ~ 30ºC
Read/Write
7 SET_LOUVER
Louver setting
0 ~ 7 (7 is Auto)
Read/Write
8 SET_CENTRAL
Central Setting:
Bit 0: ON/OFF (always can be stopped)
Bit 1: Mode
Bit 2: Setting temperature
Bit 3: Fan
Read/Write
9 READ_ONOFF
ON/OFF read:
0: OFF
1: ON
Read
10 READ_MODE
Mode read:
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Read
11 READ_FAN
Fan read
0: Low
1: Medium
2: High
Read
12 READ_TSET
Setting temperature read
(17ºC to 30ºC)
Read
13 READ_LOUVER
Louver read
0 ~ 7 (7 is Auto)
Read
14 RCS_GROUP
Remote controller group
0 ~ 255
Read
15 TIN Inlet temperature (Note 2) Read
16 TOUT Outlet temperature (Note 2) Read
17 TGAS Gas pipe temperature (Note 2) Read