CONFIGURATION 
Part. No. 2400M2501_6    Touchpoint Pro 
  97  Technical Handbook 
Table 20.  Modbus System Summary 
 
Table 21.  Modbus System Summary Continued 
 
Safe State 
Summary 
(Future 
Use) 
Table 22.  Modbus System Summary Continued 
11.2  Modbus Register Allocation for Function 04 – Read Input Registers 
There are three sets of input registers for each channel: 
1.   The analogue signal expressed as a 16 bit signed integer value. 
2.   The analogue signal expressed as a 32 bit floating point value. 
3.   An animation value. 
 
11.2.1  Analogue Registers (Integer) 
This register contains the indicated measured value in steps of 0.1 measurement units (e.g. PPM, LEL). This register should 
not be used on channels where the parameter "Gas Range Max" is set to values greater than 1000.  
Table 23.  Modbus Channel Analogue Values 
Note: The Integer format is a 16 bit signed integer.  
11.2.2  Analogue Registers (Float) 
Table 24.  Modbus Channel Analogue Values (Float) 
Note: The Float format is a 32 bit floating point value in accordance with IEEE 754-2008.