EasyManua.ls Logo

Inovance MD800 Series - Page 195

Inovance MD800 Series
565 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Para.
No.
Address
Name
Value Range
Default
Unit
Change
Page
A9-07 43271
Field control bandwidth
of asynchronous motor
in SVC mode
0.0 to 8.0 2.0 - At once
A9-07
on page
363
A9-08 43272
Low-speed running
current of asynchronous
motor in SVC mode
30 to 170 100 - At once
A9-08
on page
363
A9-09 43273
Switchover frequency of
output fixed current of
asynchronous motor in
SVC mode
2.0 Hz to 100.0 Hz 3.0 Hz At once
A9-09
on page
363
A9-10 43274
Speed fluctuation
suppression coefficient
of asynchronous motor
in SVC mode
0 to 6 3 - At once
A9-10
on page
364
A9-11 43275
Acceleration/
Deceleration time of
asynchronous motor in
SVC mode
0.1s to 3000.0s 20.0 s At once
A9-11
on page
364
A9-12 43276
Quick auto-tuning of
stator resistance before
asynchronous motor
startup
0: Disabled
1: Enabled
0 - At once
A9-12
on page
364
A9-13 43277
Coefficient 1 of quick
auto-tuning of
asynchronous motor
stator resistance
0 to 65535 10 -
At stop
A9-13
on page
364
A9-14 43278
Coefficient 2 of quick
auto-tuning of
asynchronous motor
stator resistance
0 to 65535 10 -
At stop
A9-14
on page
364
A9-15 43279
Coefficient 3 of quick
auto-tuning of
asynchronous motor
stator resistance
0 to 65535 0 -
At stop
A9-15
on page
365
A9-17 43281
Synchronous motor real-
time angle
0 to 65535 0 -
Unchangeable
A9-17
on page
365
A9-18 43282
Initial angle detection of
synchronous motor
0: Detected upon running
1: Not detected
2: Detected upon initial running after
power-on
0 - At once
A9-18
on page
365
A9-20 43284
Field weakening mode
0: Automatic mode
1: Synchronous motor adjustment
mode
2: Synchronous motor hybrid mode
3: Disabled
1 -
At stop
A9-20
on page
365
List of Drive Unit Parameters
-194-

Table of Contents

Other manuals for Inovance MD800 Series