Status displays
© 2022 KEB Automation KG
199
ru75
global drive state
Bit 0…3
ready for modulation state
Bit
Valu
e
Mult.
Plaintext
Notes
0…3
0
0
RFM
Modulation release can be made directly with setting the enable modu-
lation bit in the controlword
0
1
1
E,ru01
There is an error. => ru01
1
1
2
E.uic
The DC link in the power unit has not been charged. The voltage is be-
low the UP level. ru04 is unequal to 4 "run“
2
1
4
E.STO
At least one STO input is not set. => ru18
3
8
Reserved
5.8.1.2 Display of the state machine (4 Bits)
This 4 bits displays the actual state of the state machine.
ru75
global drive state
Bit 4…7
state machine display
Bit
Valu
e
Mult.
Plaintext
4…7
0
16
initialization
The meaning and the values are identical with
the description of st12.
The detailed description of the single states of
the state machine and the changes can be
found in chapter 4.1 State machine
1
not ready to switch on
2
switch on disable
3
ready to switch on
4
switched on
5
operation enabled
6
quick stop active
7
fault reaction active
8
fault
9
shutdown active
10
disable operation active
11
start operation active
12
mod off pause active
13
power off active
5.8.1.3 exception State (8 Bit)
The actual ru01 error message is displayed in these 8 bits. The value is identical to
ru01, but it is multiplied with 256 to be displayed in bits 8...15 of ru75.

Table of Contents

Other manuals for KEB COMBIVERT F6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F6 and is the answer not in the manual?

KEB COMBIVERT F6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F6
CategoryController
LanguageEnglish

Related product manuals