6.2.21.3 Task setting and synchronous fieldbus operation
For the influences of the task setting on the fieldbus operation please also read the
manual ma_dr_x6_fbs_phb_20191938_en.
The minimum value for synchronous fieldbus operation is dependent on is22.
The changeover of the basic process time has the following effects on the synchro-
nous PDOs:
➢ The minimum value for synchronous fieldbus operation is equal
to the cycle time of the middle interrupt level (the task "mid irq)
mid irq = minimum
cycle time PDOs
0: 62.5 µs / 16 kHz, 8 kHz, 4 kHz, 2 kHz + 8 x TpBase
7: 100 µs / 10 kHz, 5 kHz, 2.5 kHz, 1.25 kHz + 4 x
TpBase
4: 62.5 µs / 16 kHz, 8 kHz, 4 kHz, 2 kHz + 4 x TpBase
250µs
(only control type P)
Further allowed values for the sync interval are multiples of "mid irq“. With is22 = 0,
multiples of 500µs, i.e. 1ms, 1.5ms etc.
minimum sync interval all cards
Minimum sync interval P card
The following sync intervals, which represent an integer multiple of 1ms, are
possible for the switching frequency groups for all control types:
selectable switching frequencies
16 kHz, 8 kHz, 4 kHz, 2 kHz
12 kHz, 6 kHz, 3 kHz, 1.5 kHz
12 kHz, 6 kHz, 3 kHz, 1.5 kHz
14 kHz, 7 kHz, 3.5 kHz, 1.75 kHz
10 kHz, 5 kHz, 2.5 kHz, 1.25 kHz
Is possible with all settings of is22 for all switching frequencies