ru01
Error text (continuation)
Description
st01
68
ERROR overcurrent Brake
Overcurrent at the brake output
0x1000
83
ERROR Limit Switch Forward
positive (hardware) limit switch released
0x1000
84
ERROR Limit Switch Reverse
negative (hardware) limit switch released
0x1000
85
ERROR Override Limit Switch For-
ward
positive (hardware) limit switch override out of the
range of hm19
0x1000
86
ERROR Override Limit Switch Re-
verse
negative (hardware) limit switch override out of the
range of hm20
0x1000
87
ERROR Limit Switch
Ether both (hardware) limit switches released or
one (hardware) limit switch released and only the
actual direction of rotation corresponds to the limit
switch direction
0x1000
89
ERROR at encoder type change
Incompatible encoder interface and drive software
versions
0x1000
90
ERROR enc.intf.fast comm.
Communication error control board-encoder inter-
face
0x1000
91
init encoder interface
Encoder interface in initialisation routine
0x1000
92
ERROR encoder A
Error encoder A
Hardware defect or incorrect
setting of the encoder parame-
ters (type, increments per revo-
lution, etc.)
0x1000
93
ERROR encoder B
Error encoder B
0x1000
94
init encoder A
Initialisation encoder A is running
0x1000
95
init encoder B
Initialisation encoder B is running
0x1000
96
ERROR encoder missing
No encoder type is selected in ec16 in a mode that
requires an encoder
0x1000
97
ERROR overspeed (EMF)
pn72 overspeed level (EMF) has been exceeded
0x1000
98
ERROR encoder A changed
Encoder A changed
Serial number read by the
encoder is not equal to the
stored serial number (ec48 !=
ec49)
0x1000
99
ERROR encoder B changed
Encoder B changed
0x1000
100
ERROR overcurrent out1
Overcurrent at digital output 1
0x1000
101
ERROR overcurrent out2
Overcurrent at digital output 2
0x1000
102
ERROR overcurrent out3
Overcurrent at digital output 3
0x1000
103
ERROR overcurrent out4
Overcurrent at digital output 4
0x1000
105
ERROR overcurrent encoder
Overcurrent at encoder interface
0x1000
106
ERROR overcurrent 24V
Overcurrent at 24V outputs of the control terminal
block
0x1000
107
ERROR over frequency
The maximum output frequency de120 has been
exceeded. (599Hz)
0x1000
108
reset E. overheat intern CB
Overtemperature control board decreased
0x1000
109
ERROR overheat internal CB
Overtemperature internal control board
0x1000
110
ERROR OH ramp
Maximum available time between the occurrence of
an overtemperature error and the modulation
switching off has expired
0x1000
111
ERROR OHI ramp
0x1000
112
ERROR 24V supply low
24V supply has dropped to a value lower than 18V
0x1000

Table of Contents

Other manuals for KEB COMBIVERT F6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F6 and is the answer not in the manual?

KEB COMBIVERT F6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F6
CategoryController
LanguageEnglish

Related product manuals