8400 StateLine C | Reference manual
Motor control (MCTRL)
V/f characteristic control (VFCplus)
128 L Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011
5.4.2 Basic settings
The "Initial commissioning steps" listed in the table below are sufficient for a simple
characteristic control.
Detailed information on the individual steps can be found in the following
subchapters.
Tip!
Information on the optimisation of the control mode and the adaptation to the
real application is provided in the chapter "Optimising the control mode
". ( 131)
Parameterisable additional functions are described correspondingly in the chapter
"Parameterisable additional functions
". ( 193)
Initial commissioning steps
1. Defining the V/f characteristic shape
. ( 129)
2. Defining current limits (Imax controller)
. ( 130)