Commissioning
Safety instructions with regard to commissioning
48 L Firmware 11.00 - DMS 8.0 EN - 10/2011
3.1 Safety instructions with regard to commissioning
General safety instructions
To avoid injury to persons or damage to material assets,
check before connecting the mains voltage
the wiring for completeness, short circuit, and earth fault
the "emergency stop" function of the entire system
that the motor circuit configuration (star/delta) is adapted to the output voltage of
the controller
the in-phase connection of the motor
check the setting of the most important drive parameters before enabling the
controller:
the V/f rated frequency must be adapted to the motor circuit configuration!
the drive parameters relevant for your application must be set correctly!
the configuration of the I/O terminals must be adapted to the wiring!
ensure that there are no active speed setpoints before enabling the controller
.
Safety instructions with regard to motor operation
Danger!
Continuous operation of self-ventilated motors at small field frequencies and
rated motor currents is not permissible for thermal reasons!
In the Lenze setting, the Motor temperature monitoring (PTC)
is activated.
( 236)
Activate the Brake resistor monitoring (I2xt)
if necessary. ( 237)
C00015
must be used to select 87 Hz operation if a delta-connected
asynchronous motor (nameplate data: 400 V
/230 V
) is to be operated in
conjunction with a drive controller for a mains voltage of 400 V.