Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011 L 219
8400 StateLine C | Reference manual
Motor control (MCTRL)
Encoder/feedback system
5.10.1 Parameterising digital inputs as encoder inputs
The function of the digital inputs DI1/DI2 is defined in C00115/1
.
To be able to use the digital inputs as encoder inputs, select 2, 3 or 4 (Lenze
recommendation: 2) in C00115/1
depending on the input terminals used.
Related topics:
Digital terminals
( 254)
Using DI1 and DI2 as frequency inputs
( 259)
Selection in C00115/1 Function
2: (DI1/DI2)=FreqIn12 (2-track) DI1 and DI2 = 2-track frequency input
• Permits a two-track evaluation of the encoder including correct
detection of the direction of rotation.
3: (DI1/DI2=+-)=FreqIn12 DI1 = 1-track frequency input
DI2 = direction
4: DI1=CountIn1 | DI2=In2 DI1 = counter input
DI2 = digital input
Danger!
For single-track evaluation, make sure that the sign is correctly specified.
Otherwise, the motor may overspeed.
Note!
If the digital inputs are parameterised as encoder inputs, the corresponding
output signals (bIn1/bIn2) at the LS_DigitalInput
system block are automatically
set to FALSE.
The wiring diagram and the assignment of the input terminals can be found in
the 8400 hardware manual.
• The hardware manual has been stored in electronic form on the data carrier
supplied with the 8400 drive controller.