8400 StateLine C | Reference manual
Function library
Function blocks | L_MPot_1
812 L Firmware 11.00 - DMS 8.0 EN - 10/2011
16.1.23.2 Deactivate motor potentiometer
When the motor potentiometer is deactivated by setting bInAct to TRUE, the nOut_a
output signal responds according to the function selected via Function.
[16-12] Example: Deactivation of the motor potentiometer when the Function = 1 has been selected
When the motor potentiometer is deactivated, nOut_a is reduced to 0 % with the deceleration time wTif.
If it is activated again, nOut_a is increased again to nLowLimit with the acceleration time wTir.
nOut_a
t
t
TRUE
FALSE
bUp
t
TRUE
FALSE
bDown
nHighLimit
nLowLimit
0
wTir
wTif
wTir
t
TRUE
FALSE
bInAct
wTif
wTif