Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011 L 91
8400 StateLine C | Reference manual
Device control (DCTRL)
Device state machine and device statuses
4.2.5 ReadyToSwitchOn
The controller is in this device status directly after the initialisation has been completed!
The bus systems are running and the terminals and encoders are evaluated.
The monitoring modes are active.
The controller can be parameterised.
The application is basically executable.
LED DRIVE READY LED DRIVE ERROR Display in C00137 Display in status word 1 (C00150)
Bit 11 Bit 10 Bit 9 Bit 8
OFF ReadyToSwitchOn 0 0 1 1
Note!
• The "ReadyToSwitchOn" status is not only activated after the mains
connection, but also after the deactivation of "Trouble
", "Fault" or
"SafeTorqueOff
".
•If C00142
activates the autostart option "Inhibit at power-on" (Lenze setting),
explicit deactivation of the controller inhibit after mains connection is always
required for the controller to change from the "ReadyToSwitchOn" status to
the "SwitchedOn
" status.
• If only the 24V voltage supply is available during the mains connection, the
error message "LU: Undervoltage in the DC bus
" is entered into the logbook of
the drive controller and the drive controller remains in the
"ReadyToSwitchOn" status.
Danger!
If the "Inhibit at power-on" auto-start option has been deactivated in C00142,
the "ReadyToSwitchOn" status switches directly to the SwitchedOn
" status after
mains connection.
Automatic restart after mains connection/fault...
( 97)