8400 StateLine C | Reference manual
Device control (DCTRL)
Device commands (C00002/x)
80 L Firmware 11.00 - DMS 8.0 EN - 10/2011
4.1.2 Load all parameter sets
The C00002/6
= "1: On / start" device command reloads all parameter settings from the
memory module to the controller.
Can only be executed if the controller is inhibited; otherwise, the feedback C00002/6
= "6: No access - controller inhibit" will be returned.
All parameter changes which have been carried out after the last time the parameter
set was saved will be lost!
This device command has an effect on the settings of the parameters of the operating
system, application and module.
How to load the parameter settings from the memory module:
1. If the controller is enabled, it must be inhibited, e.g. by executing the
"Enable/Inhibit controller" device command "(C00002/16
= "0: Off / ready").
2. Execute the "Load all parameter sets" device command:
C00002/6
= "1: On / start"
The loading process may take a couple of seconds. After the device command has
been called, C00002/6
returns dynamic status information ("Work in progress
20 %" "Work in progress 40 %" "Work in progress 60 %", etc.).
Note!
The controller is currently provided with one data record for all parameters, i.e.
every parameter has a value. Several data records per controller are in
preparation.
From version 04.00.00, the basic function Parameter change-over
enables a
change-over between four sets with different parameter values for up to 32
freely selectable parameters.
( 509)