Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011 L 197
8400 StateLine C | Reference manual
Motor control (MCTRL)
Parameterisable additional functions
All other types of control require the following settings in addition:
Parameter Info Required setting
C00022
Imax in motor mode higher than rated motor current
(max. 160 % rated motor current)
C00081
Rated motor power adapt motor data
(see motor nameplate),
then carry out identification run
Automatic motor data
identification ( 112)
C00087
Rated motor speed
C00088
Rated motor current
C00089
Rated motor frequency
C00090
Rated motor voltage
C00091
Motor cos ϕ