8400 StateLine C | Reference manual
I/O terminals
Digital terminals
264 L Firmware 11.00 - DMS 8.0 EN - 10/2011
Internal interfaces to the application
Relevant inputs at the LS_DigitalInput
system block:
Relevant outputs at the LS_DigitalInput
system block:
Identifier
DIS code | data type
Information/possible settings
Counting input DI1
bCountIn1_ResetCompare
BOOL
Reset status signal "Comparison value reached"
FALSEÊTRUE The output bCountIn1_Compare is reset to FALSE.
bCountIn1_LoadStartValue
BOOL
Load starting value into counter
FALSEÊTRUE The starting value set in C02840/1
is accepted as the current count
value.
Identifier
DIS code | data type
Value/meaning
Counting input DI1
bCountIn1_Compare
BOOL
Status signal "Comparison value reached"
FALSE Current count value < comparison value (C02840/2
)
TRUE Current count value comparison value (C02840/2
)
wCountIn1_HW
wCountIn1_LW
C02841/1 | WORD
Current count value
Output as High and Low word (without sign)
Possible counting range: 0 ... 2
31
-1