8400 StateLine C | Reference manual
I/O terminals
Digital terminals
Calculation of the output signal
The output value at dnPosIn12_p is calculated as per the formula below:
Example
You want to determine the counter content of the integrator at a certain speed at the input
and a certain integration time t.
Given values:
nFreqIn12_v = 1000 rpm integer value 1092
Integration time t = 10 s
Starting value of the integrator = 0
Solution:
Conversion of the nFreqIn12_v input signal:
Calculation of the output value:
t = integration time
16384 15000 rpm
1 1 incr.
dnPosIn12_p [incr.] nFreqIn12_v [rpm] t [s] 65535 [incr./rev.]⋅⋅=
1000 rpm
1000 rev.
60 s
-----------------------=
dnPosIn12_p
1000 rev.
60 s
-----------------------
10 s
65535 incr.
Rev.
----------------------------
⋅⋅ 10922666 incr.==