Firmware 11.00 - DMS 8.0 EN - 10/2011 L 411
8400 StateLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
ot1: Maximum torque reached [xx.0123.00001]
oC7: Motor overcurrent [xx.0123.00007]
oU: DC bus overvoltage [xx.0123.00014]
LU: DC bus undervoltage [xx.0123.00015]
Response (Lenze setting printed in bold) Setting: C00608 (; Adjustable response)
: 0: No Reaction ; 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked ; 5: Warning 6: Information
Cause Remedy
The device indicates that the maximally possible torque
at the motor shaft has been reached.
C00057
displays the current torque.
Reduce motor load.
Response (Lenze setting printed in bold)
0: No Reaction : 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The maximum current monitoring has tripped.
The instantaneous value of the motor current has
exceeded the limit value set in C00939
.
Check and, if required, correct dimensioning of the load
with regard to the installed device power.
Response (Lenze setting printed in bold)
0: No Reaction ; 1: Fault : 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The device has detected an overvoltage in the DC bus. To
protect the device hardware, the inverter control is
switched off.
Depending on the configuration of the auto-start lock
function, C00142
serves to set that, if this error has
been tripped, the controller only starts after the
controller inhibit is switched.
If this error message remains active longer than the
time set in C00601
, a "Fault" is tripped.
Reduce load in generator mode.
Use a brake resistor.
Use a regenerative power supply unit.
Establish a DC-bus connection.
Response (Lenze setting printed in bold) Setting: C00600/1 (; Adjustable response)
0: No Reaction ; 1: Fault : 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The device has detected a DC bus undervoltage. The
inverter control is switched off because the drive
properties of the motor control cannot be provided
anymore due to the DC bus undervoltage.
Depending on the configuration of the auto-start lock
function, C00142
serves to set that, if this error has
been tripped, the controller only starts after the
controller inhibit is switched.
Switch on mains supply or ensure sufficient supply via
DC bus.
Adjust setting in C00142
if required.