8400 StateLine C | Reference manual
Commissioning
PC manual control
70 L Firmware 11.00 - DMS 8.0 EN - 10/2011
How to activate PC manual control:
1. If an online connection to the controller has not been established yet:
Go online.
2. Go to Workspace and change to the Application parameters tab.
3. Go to the Overview dialog level and click the "PC manual control" button.
The following safety note is displayed first:
Click the Cancel button to abort the action and close the dialog box.
•The Timeout monitoring input field serves to adapt the timeout for monitoring
the connection between the PC and the controller.
Note!
For activated PC manual control:
The online connection between the PC and the controller is monitored by the
controller.
If the online connection is interrupted for longer than the set timeout (Lenze
setting: 2 s):
Error response "Fault" is triggered, i.e. the motor becomes torqueless and is
coasting unless it already is at standstill.
–The "Ck16: Time overflow manual control
" error message is entered into
the logbook.
PC manual control provides the Motion Control Kernel and the motor interface
with all required control signals and setpoint signals.
The existing application (function block interconnection) is now decoupled
from these interfaces but will be processed as before and remains
unchanged.
It does not matter what type of motor control is set in C00006
.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com