C00242 Operating mode
Lenze setting: "0: Off"
0 Off The input setpoint nNSet_a is output
without any changes at the output
nOut_a.
1nNSet + nNSet_PID nNSet_a and nAct_a are used as PID
input values. The arriving nNSet_a is
additively linked to the value output
by the PID element.
2nSet_PID nSet_a and nAct_a are used as PID
input values. The input nNSet_a is
not considered.
3nNSet_PID nNSet_a and nAct_a are used as PID
input values. The input nSet_a is not
considered.
4 nNSet + nSet_PID nSet_a and nAct_a are used as PID
input values. The arriving nNSet_a
setpoint is additively linked to the
value output by the PID element.
5 nNSet || nSet_PID nSet_a and nAct_a are used as PID
input values. The setpoint nNSet_a is
output at the output nOut_a . The
PID output value is output at the
output nPIDOut_a.
C00243
0.000 s 999.999 Influence acceleration time
Acceleration time T
ir
for the
influencing factor.
Lenze setting: 5.000 s
C00244
0.000 s 999.999 Influence deceleration time
Deceleration time T
if
for the
influencing factor.
Lenze setting: 5.000 s
C00245
-199.99 % +199.99 Display of PID output value
nPIDOut_a
C00247
(from version 06.00.00)
0 % 100 Window for comparison function
"Actual value = setpoint"
Lenze setting: 2 %
Hysteresis: 1 % (fixed)
Parameter Possible settings Info