Firmware 11.00 - DMS 8.0 EN - 10/2011 L 95
8400 StateLine C | Reference manual
Device control (DCTRL)
Device state machine and device statuses
4.2.10 Trouble
This device status becomes active as soon as a monitoring mode responds for which the
error response "Trouble" has been parameterised.
The motor has no torque (is coasting) due to the inhibit of the inverter.
The "Trouble" device status is automatically abandoned if the error cause has been
removed.
Depending on certain conditions a status change takes place based on the "Trouble" device
status.
Related topics:
wCANControl/wMCIControl control words
( 103)
Basics on error handling in the controller
( 380)
Error messages of the operating system
( 401)
LED DRIVE READY LED DRIVE ERROR Display in C00137 Display in status word 1 (C00150)
Bit 11 Bit 10 Bit 9 Bit 8
OFF Trouble 0111
Note!
If the "Inhibit at trouble" auto-start option has been activated in C00142, explicit
deactivation of the controller inhibit is required before this status can be
abandoned.
Change condition Changeover to the device status
The error cause is no longer active. ReadyToSwitchOn
Control bit "EnableOperation" of all control channels = "1"
AND terminal RFR = HIGH level (controller enable)
AND the message has been cancelled.
OperationEnabled
Control bit "EnableOperation" of a control channel = "0"
OR terminal RFR = LOW level (controller inhibit)
AND the message has been cancelled.
SwitchedOn
In the system, there is an error configured on "TroubleQSP".
AND the message has been cancelled.
TroubleQSP