33186 0x81A2 Modbus: incorrect request by master Keypad display: Modbus r
equest
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
The r
equest by the master is invalid, e. g. invalid
CRC checksum, non-supported funcon code,
or impermissible data access.
Check request by the master:
•
Value in the valid range?
•
Funcon code valid?
•
No impermissible write access? (e. g. with
regard to read-only parameters)
Warning
The inverter (slave) responds to the master with
an error code:
•
0x01 = invalid funcon code
•
0x02 = invalid data address
•
0x03 = invalid data value
•
0x04 = slave device failure
33425 0x8291 CAN: RPDO1 me-out Keypad display: Timeout RPDO1
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
Fault (congurable)
Seng parameters: 0x2857:001
33426 0x8292 CAN: RPDO2 me-out Keypad display: Timeout RPDO2
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
Fault (congurable)
Seng parameters: 0x2857:002
33427 0x8293 CAN: RPDO3 me-out Keypad display: Timeout RPDO3
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
Fault (congurable)
Seng parameters: 0x2857:003
33553 0x8311 Torque limit reached Keypad display: T
orque limit
Cause Remedy Error type/response
Motor has reached the torque limit:
•
0x2949:003
(P337.03): Actual posive torque
limit
•
0x2949:004 (P337.04): Actual negave
torque limit
•
Ob
serve load requirements.
•
Reduce motor load.
•
Check set torque limits and sources for the
torque limits.
No response
(congurable)
Seng parameters: 0x2D67:001 (P329.01)
Related topics
4Mot
or torque monitoring ^ 197
33664 0x8380 Funcon not allowed in selected operang mode Keypad display: Func. n. allo
wed
Cause Remedy Error type/response
The selected
funcon is not permissible in the
chosen operang mode.
•
Selecon of torque mode [-1] in 40x6060
(P301.00) with
incompable motor control in
40x2C00 (P300.00).
•
Selecon of invalid drive mode [0] in
40x6060
(P301.00).
•
Not
e: selecon of torque mode [-1] in
40x6060
(P301.00) with incompable motor
c
ontrol in 40x2C00 (P300.00).
•
Check
sengs of operaon modes.
•
0x6060 (P301.00)0x6060 (P301.00)
Warning
Diagnoscs and fault eliminaon
Error codes, causes and remedies
303