Table of Functions
203
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F SL Ref.
07 0h1C07 Base frequency
M2-Base
Freq
30.00-
400.00(Hz)
60.00 X O I -
08 0h1C08 Control mode
M2-Ctrl
Mode
0
V/F
0:V/F X O I -
2
Slip
Compen
4
IM
Sensorless
10 0h1C0A
Number of
motor poles
M2-Pole
Num
2-48
Depen
dent
on
motor
setting
s
X O I -
11 0h1C0B Rated slip speed
M2-Rated
Slip
0-3000(rpm) X O I -
12 0h1C0C
Motor rated
current
M2-Rated
Curr
1.0-1000.0(A) X O I -
13 0h1C0D
Motor no-load
current
M2-Noload
Curr
0.5-1000.0(A) X O I -
14 0h1C0E
Motor rated
voltage
M2-Rated
Volt
170-480(V) X O I -
15 0h1C0F Motor efficiency
M2-
Efficiency
64-100(%) X O I -
16
0h1C10
Load inertia rate
M2-Inertia Rt
0-8
X
O
I
-
17
-
Stator resistor
M2-Rs
Dependent
on motor
settings
X
O
I
-
18 -
Leakage
inductance
M2-Lsigma X O I -
19 -
Stator
inductance
M2-Ls X O I -
20
55
-
Rotor time
constant
M2-Tr 25-5000(ms) X O I -
25 0h1C19 V/F pattern M2-V/F Patt
0 Linear
0:
Linear
X O I -
1 Square
2 User V/F
26 0h1C1A
Forward Torque
boost
M2-Fwd
Boost
0.0-15.0(%)
2.0
X O I -
27 0h1C1B
Reverse Torque
boost
M2-Rev
Boost
0.0-15.0(%) X O I -
28 0h1C1C
Stall prevention
level
M2-Stall Lev 30-150(%) 150 X O I -
29 0h1C1D
Electronic
thermal 1
minute rating
M2-ETH
1min
100-200(%) 150 X O I -
55
Displayed when M2-08 is set to 4 (IM Sensorless)