4.1.3.2 Setting a Frequency Reference for -10–10 V Input
Set the 07 (Frequency reference source) code in the DRV group to 2 (V1), and then set code 06 (V1
Polarity) to 1 (bipolar) in the Input Terminal group (IN). Use the output voltage from an external
source to provide input to V1.
[V1 terminal wiring]
[Bipolar input voltage and output frequency]
DRV 07
Frequency reference
source
Freq Ref Src 2 V1 0–12 -
IN
01
Frequency at maximum
analog input
Freq at 100%
60.00
Hz
06
V1 Polarity 1 Bipolar 0–1 -
13
V1 output at minimum
voltage (%)
V1- Perc y1 0.00 -100.00–0.00% %
15
V1 output at maximum
voltage (%)
V1- Perc y2 -100.00 -100.00–0.00% %