EasyManua.ls Logo

Micom P634 - Page 430

Micom P634
840 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Address
Default Min Max Unit Logic Diagram
Main function
MAIN: Device on-line
003 030
0: No (= off) Fig. 3-55, (p. 3-87)
[spacer]
Switching the device off-line or on-line. Some parameters can only be changed
when protection is disabled.
[spacer]
MAIN: Test mode USER
003 012
0: No Fig. 3-68, (p. 3-99)
[spacer]
When the test mode user is activated, signals or measured data for PC and
communication interfaces are labeled 'test mode'.
[spacer]
MAIN: Nominal frequ. fnom
010 030
50: 50 Hz
[spacer]
Setting for the nominal frequency of the protected system.
[spacer]
MAIN: Phase sequence
010 049
1: A - B - C
[spacer]
Setting the phase sequence A-B-C or A-C-B.
(Alternative terminology: Setting for the rotary field's direction, either clockwise
or anticlockwise.)
[spacer]
MAIN: Inom C.T.prim.,end a
019 020
200 1 50000 A Fig. 3-46, (p. 3-78)
[spacer]
MAIN: Inom C.T.prim.,end b
019 021
200 1 50000 A
[spacer]
MAIN: Inom C.T.prim.,end c
019 022
200 1 50000 A
[spacer]
MAIN: Inom C.T.prim.,end d
019 026
200 1 50000 A
[spacer]
Setting for the primary nominal current of the main current transformer (phase
currents) of end a or b .
[spacer]
MAIN: Inom C.T.Yprim,end a
019 027
200 1 50000 A
[spacer]
MAIN: Inom C.T.Yprim,end b
019 028
200 1 50000 A
[spacer]
MAIN: Inom C.T.Yprim,end c
019 029
200 1 50000 A
[spacer]
Setting for the primary nominal current of the main current transformer at the
neutral-point-to-ground connection.
P634 7 Settings
7-76 P634/EN M/R-42-A // P634311653

Table of Contents

Related product manuals