Parameter Address
Default Min Max Unit Logic Diagram
Main function
MAIN: General reset USER
003 002
0: don't execute Fig. 3-65, (p. 3-97)
[spacer]
Reset of the following memories:
All counters
LED indicators
Operating data memory
All event memories
Event counters
Fault data
Measured overload data
Recorded fault values
[spacer]
MAIN: Reset indicat. USER
021 010
0: No Fig. 3-65, (p. 3-97)
[spacer]
Reset of the following displays:
LED indicators
Fault data
[spacer]
MAIN: Rset.latch.trip USER
021 005
0: don't execute Fig. 3-62, (p. 3-93)
[spacer]
Reset of latched trip commands from the local control panel.
[spacer]
MAIN: Reset c. cl/tr.cUSER
003 007
0: don't execute Fig. 3-63, (p. 3-94)
[spacer]
The counters for counting the close and trip commands are reset.
[spacer]
MAIN: Reset IP,max,st.USER
003 033
0: don't execute Fig. 3-46, (p. 3-78)
[spacer]
The values for the delayed stored maximum phase current are reset (for all
ends).
[spacer]
MAIN: Group reset 1 USER
005 253
0: don't execute Fig. 3-66, (p. 3-97)
[spacer]
MAIN: Group reset 2 USER
005 254
0: don't execute Fig. 3-66, (p. 3-97)
[spacer]
Group of resetting commands.
[spacer]
MAIN: Man. trip cmd. USER
003 040
0: don't execute Fig. 3-62, (p. 3-93)
[spacer]
A 100 ms trip command is issued from the local control panel.
Note: The command is only executed if the manual trip command has been
configured as trip command 1 or 2.
8 Information and Control Functions P634
P634/EN M/R-42-A // P634311653 8-155