EasyManuals Logo

Mitsubishi 700 Series User Manual

Mitsubishi 700 Series
280 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #119 background imageLoading...
Page #119 background image
PROTOCOL-SPECIFIC INFORMATION
106
Inverter registers can be addressed as holding registers (4X references) and input registers (3X
references).
Specific bits within inverter registers can be accessed as either coils (0X references) or discrete
inputs (1X references).
Write data checking is not available (refer to section 4.2.) For example, if a write is performed to a
register with a data value that is out-of-range of the corresponding parameter object, no Modbus
exception will be immediately returned.
The “unit identifier” (UI) field of the request packets is ignored and is echoed in the response.
Modbus/TCP should not be confused with Modbus (serial) over TCP. Modbus over TCP is not
compatible with Modbus/TCP and is not supported.
The driver can be configured to detect a timeout (communication loss) and perform a timeout action.
9.1.2 Holding & Input Registers
The inverter registers by default are mapped as both holding registers (4X) and input registers (3X), and
are accessed by using the inverter register numbers described in section 4.1. The 4X and 3X only serve
as a naming convention for holding register and input register respectively, and should NOT be included
as part of the actual on-the-wire register number. To further clarify, Modbus register 40201 is the same
as Modbus holding register 201. The same description applies to input registers (3X).
For example, from a Modbus/TCP masters point of view, in order to access the output frequency
(register 201) as a holding register, the Modbus/TCP master must execute the Read Multiple Registers
function code and target register 201. This will similarly apply when accessing an inverter register as an
Input Register.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi 700 Series and is the answer not in the manual?

Mitsubishi 700 Series Specifications

General IconGeneral
Control MethodVector Control
Overload Capacity150% of rated current for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Short circuit
Communication OptionsRS-485, Profibus, Ethernet
Output Power Range0.4 kW to 630 kW
Cooling MethodForced air cooling (fan) (Varies by model)
Operating Temperature-10 to +50°C (Varies by model, may be derated at higher temperatures)
Storage Temperature-20 to +65°C
Humidity95% RH or less (non-condensing)
AltitudeUp to 1000 m above sea level (Derating may be required above 1000 m)
Enclosure RatingIP20
ModelFR-A700, FR-F700, FR-E700, FR-D700, FR-S700

Related product manuals