PROTOCOL-SPECIFIC INFORMATION
226
9.9 PROFINET IO
9.9.1 Overview
The PROFINET IO device driver allows a controller to interact with the interface card via cyclic data
exchange and acyclic read/write requests. The I/O data is entirely user-configurable, and is utilized
when a standard I/O module is chosen during network configuration.
Other notes of interest include:
Allows simultaneous access to only 1 PROFINET controller.
Supports conformance class B and real time (RT) communication.
Supports the highest Netload Class III.
Supports MRP (Media Redundancy Protocol) client.
Supports DCP (Discovery Control Protocol).
Supports alarms.
Supports I&M.
The lowest supported I/O Cycle Update Time (via STEP 7 or an equivalent hardware configuration
tool) is 1ms.
The GSDML file can be obtained from the product
web page.
Supports several user configurable I/O modules with up to 32 input words and 32 output words.
Supports the PROFIdrive profile version 4.1.