PROTOCOL-SPECIFIC INFORMATION
193
9
9.4.4 Server Settings
In the studio’s Project panel, navigate to A7NETH-2PEthernetBACnet/IP Server.
UDP Port
This is the UDP port on which to transmit and receive BACnet/IP packets on the local subnet. The
default value is 47808 (0xBAC0). To ensure successful communications, use caution when using a port
setting other than the default value.
9.4.5 Node Settings
There are no node settings. A node is simply a container for objects.
9.4.6 Device Object Settings
In the studio’s Project panel, navigate to A7NETH-2P…Ethernet…BACnet/IP Server…Node…Device
Object.
A Device Object is automatically added to every node, and cannot be removed. The Device Object
contains several configurable fields that must be appropriately set for each device residing on a BACnet
network.
Device Name
Defines the node’s name. The device name must be unique across the entire BACnet network. Enter a
string of between 1 and 32 characters in length.