PROTOCOL-SPECIFIC INFORMATION
9.9.5.2 PROFIdrive Control and Status Words
The control word, STW1, is the principal means for controlling the drive. It is sent by the controller (PLC)
to the device (inverter). The bitmapping for the control word is described in Table 54. The status word,
ZSW1, returns status information from the inverter to the controller. The bitmapping for the status word
is described in Table 55.
Table 54: STW1 Control Word Mapping
0
1
2
3
Enable inverter operation
Disable inverter operation
4
Enable the ramp frequency generator (RFG)
Hold the output frequency to 0 Hz
5
1
Unfreeze the RFG
0 Freeze Ramp Generator
Freeze the RFG with the current output
frequency