PROTOCOL-SPECIFIC INFORMATION
207
9
3E/4E
Device Memory Random Write
0x1402
0x0000
360 (3E) / 358 (4E)
1E
Device Memory Batch Read
0x01
-
256
1E
Device Memory Batch Write
0x03
-
256
Table 46 lists the supported internal device memory types. There is no functional difference between the
device types. All device types are equal and simply provide access to the register mapping.
Table 46: MELSEC / SLMP Server Device Types
Device Type
3E/4E Device Code
1E Device Code
Data Type
Data Register
0xA8
0x4420
16-Bit Word
Link Register
0xB4
0x5720
16-Bit Word
Index Register
0xCC
-
16-Bit Word
File Register
0xAF, 0xB0
0x5220, 0x5A52
16-Bit Word
The device point is the register number (refer to section 4.1).
9.5.3 Server Settings
In the studio’s Project panel, navigate to A7NETH-2P…Ethernet…MELSEC/SLMP Server.
TCP Port
Defines the local TCP port (1025…65534) on which the driver will listen for connections from the client.
Ensure that this port assignment is unique, and does not conflict with ports utilized by other drivers.