PROTOCOL-SPECIFIC INFORMATION
9.2.10 ControlLogix Examples: Setup
This section will demonstrate how to initially setup a ControlLogix PLC (such as a 1756-L61) coupled
with a 1756-ENBT communication interface (adjust this procedure according to your specific
equipment). Later sections will provide specific read/write examples using this configuration with I/O or
explicit messaging.
1) Run RSLogix 5000, and create a new
configuration.
2) To add a 1756-ENBT to your I/O
configuration, first switch to offline
mode.
3) Right click on the I/O Configuration
node in the controller organizer view
and choose “New Module…”
4) The “Select Module” window will
open.
5) Select the “1756-ENBT”, and click
“Create”. Refer to Figure 30.
6) The “New Module” window will open.
Refer to Figure 31.
Figure 30: Adding a New Module