PROTOCOL-SPECIFIC INFORMATION
189
9
9.4.3 Default Supported Object Details
This section will describe the default objects details. Since the objects are configurable, the system
integrator is responsible for managing, maintaining, and documenting the actual configuration.
Binary Input Objects
BI1 ....... Indicates the status of the RUN output terminal function configured by Pr. 190 RUN terminal
function selection. Corresponds to register 100, bit 0 (bitmask 0x0001).
BI2 ....... Indicates whether the inverter is running forward. Corresponds to register 100, bit 1 (bitmask
0x0002).
BI3 ....... Indicates whether the inverter is running reverse. Corresponds to register 100, bit 2 (bitmask
0x0004).
BI4 ....... Indicates the status of the SU output terminal function configured by Pr. 191 SU terminal function
selection. Corresponds to register 100, bit 3 (bitmask 0x0008).
BI5 ....... Indicates the status of the OL output terminal function configured by Pr. 193 OL terminal function
selection. Corresponds to register 100, bit 4 (bitmask 0x0010).
BI6 ....... Indicates the status of the IPF output terminal function configured by Pr. 192 IPF terminal function
selection. Corresponds to register 100, bit 5 (bitmask 0x0020).
BI7 ....... Indicates the status of the FU output terminal function configured by Pr. 194 FU terminal function
selection. Corresponds to register 100, bit 6 (bitmask 0x0040).