PROTOCOL-SPECIFIC INFORMATION
BI8 ....... Indicates the status of the ABC1 output terminal function configured by Pr. 195 ABC1 terminal
function selection. Corresponds to register 100, bit 7 (bitmask 0x0080).
BI9 ....... Indicates the status of the ABC2 output terminal function configured by Pr. 196 ABC2 terminal
function selection. Corresponds to register 100, bit 8 (bitmask 0x0100).
BI10 ..... Indicates whether or not the inverter is in an alarm condition. Corresponds to register 100, bit 15
(bitmask 0x8000).
Binary Output Objects
BO1 ..... Activates the AU input terminal function configured by Pr. 184 AU terminal function selection.
Corresponds to register 1, bit 0 (bitmask 0x0001).
BO2 ..... Forward command. Corresponds to register 1, bit 1 (bitmask 0x0002).
BO3 ..... Reverse command. Corresponds to register 1, bit 2 (bitmask 0x0004).
BO4 ..... Activates the RL input terminal function configured by Pr. 180 RL terminal function selection.
Corresponds to register 1, bit 3 (bitmask 0x0008).
BO5 ..... Activates the RM input terminal function configured by Pr. 181 RM terminal function selection.
Corresponds to register 1, bit 4 (bitmask 0x0001).
BO6 ..... Activates the RH input terminal function configured by Pr. 182 RH terminal function selection.
Corresponds to register 1, bit 5 (bitmask 0x0001).