PROTOCOL-SPECIFIC INFORMATION
BO7 ..... Activates the RT input terminal function configured by Pr. 183 RT terminal function selection.
Corresponds to register 1, bit 7 (bitmask 0x0001).
BO8 ..... Activates the MRS input terminal function configured by Pr. 187 MRS terminal function selection.
Corresponds to register 1, bit 10 (bitmask 0x0001).
BO9 ..... Activates the JOG input terminal function configured by Pr. 185 JOG terminal function selection.
Corresponds to register 1, bit 6 (bitmask 0x0001).
BO10 ... Activates the CS input terminal function configured by Pr. 186 CS terminal function selection.
Corresponds to register 1, bit 9 (bitmask 0x0001).
BO11 ... Activates the STOP input terminal function configured by Pr. 188 STOP terminal function selection.
Corresponds to register 1, bit 11 (bitmask 0x0001).
BO12 ... Activates the RES input terminal function configured by Pr. 189 RES terminal function selection.
Corresponds to register 1, bit 12 (bitmask 0x0001).
Analog Input Objects
AI1 ....... The output frequency of the inverter in 0.01 Hertz units (6000=60.00Hz). Corresponds to
register 201.
AI2 ....... The output current of the inverter in 0.1 or 0.01 Amp units (depends on inverter capacity).
Corresponds to register 202.
AI3 ....... The output voltage of the inverter in 0.1 Volt units (1000=100.0V). Corresponds to register 203.