PROTOCOL-SPECIFIC INFORMATION
AI4 ....... Input power of the inverter in 0.1 or 0.01 kW units (depends on inverter capacity). Corresponds
to register 213.
AI5 ....... Output power of the inverter in 0.1 or 0.01 kW units (depends on inverter capacity).
Corresponds to register 214.
AI6 ....... Energy consumption in kWh. Corresponds to register 225.
AI7 ....... Inverter operation mode status. Corresponds to register 101.
AI8 ....... PID set point monitor in 0.1% units. Corresponds to register 252.
AI10 ..... PID measurement value monitor in 0.1% units. Corresponds to register 253.
AI11 ..... PID deviation value monitor in 0.1% units. Corresponds to register 254.
Analog Output Objects
AO1 ..... The frequency command (RAM) of the inverter in 0.01 Hertz units. Corresponds to register 2.
AO2 ..... The frequency command (EEPROM) of the inverter in 0.01 Hertz units. Corresponds to register
3.
AO3 ..... Selects the operation mode of the inverter. Corresponds to register 4.
AO4 ..... Inverter fault reset command. Corresponds to register 5.
AO5 ..... Alarm clear command. Corresponds to register 6.
AO6 ..... All parameter clear command. Corresponds to register 7.