PROTOCOL-SPECIFIC INFORMATION
185
9
9.4.2 Default Supported Objects
This section will describe the default objects. Since the objects are configurable, the system integrator is
responsible for managing, maintaining, and documenting the actual configuration. Always use the studio
to confirm the configuration before commissioning the device.
Table 41: Binary Input Object Instance Summary
Instance ID Object Name Description
Active/
Inactive Text
BI1
RUN_ STATUS
Run status
running/stopped
BI2
FOR_ROT_STATUS
Forward rotation status
forward/off
BI3
REV_ROT_STATUS
Reverse rotation status
reverse/off
BI4
SU_STATUS
Up to frequency
on/off
BI5
OVERLOAD_STATUS
Overload status
on/off
BI6
IPF_STATUS
Instantaneous power failure
on/off
BI7
FU_STATUS
Frequency detection
on/off
BI8
ABC1_STATUS
Terminal function selection status
on/off
BI9
ABC2_STATUS
Terminal function selection status
on/off
BI10
ALARM_OCC_STATUS
Alarm occurrence status
on/off