EasyManua.ls Logo

Omron 3G3RX - Page 307

Omron 3G3RX
452 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-188
4-4 Communication Function
4
Functions
1226h
Multi-step speed
reference 8
A028
(HIGH)
R/W
0/Starting frequency to Max. frequency
0.01
[Hz]
1227h
A028
(LOW)
R/W
1228h
Multi-step speed
reference 9
A029
(HIGH)
R/W
0/Starting frequency to Max. frequency
0.01
[Hz]
1229h
A029
(LOW)
R/W
122Ah
Multi-step speed
reference 10
A030
(HIGH)
R/W
0/Starting frequency to Max. frequency
0.01
[Hz]
122Bh
A030
(LOW)
R/W
122Ch
Multi-step speed
reference 11
A031
(HIGH)
R/W
0/Starting frequency to Max. frequency
0.01
[Hz]
122Dh
A031
(LOW)
R/W
122Eh
Multi-step speed
reference 12
A032
(HIGH)
R/W
0/Starting frequency to Max. frequency
0.01
[Hz]
122Fh
A032
(LOW)
R/W
1230h
Multi-step speed
reference 13
A033
(HIGH)
R/W
0/Starting frequency to Max. frequency
0.01
[Hz]
1231h
A033
(LOW)
R/W
1232h
Multi-step speed
reference 14
A034
(HIGH)
R/W
0/Starting frequency to Max. frequency
0.01
[Hz]
1233h
A034
(LOW)
R/W
1234h
Multi-step speed
reference 15
A035
(HIGH)
R/W
0/Starting frequency to Max. frequency
0.01
[Hz]
1235h
A035
(LOW)
R/W
1236h Not used 
1237h Not used 
1238h Jogging frequency A038 R/W Starting frequency to 999
0.01
[Hz]
1239h Jogging stop selection A039 R/W
00: FRS (Free-running on jogging stop/
Disabled in operation)
01: DEC (Deceleration stop on jogging
stop/Disabled in operation)
02: DB (DC injection braking on jogging
stop/Disabled in operation)
03: FRS (RUN) (Free running on jogging
stop/Enabled in operation)
04: DEC (RUN) (Deceleration stop on
jogging stop/Enabled in operation)
05: DB (RUN) (DC injection braking on
jogging stop/Enabled in operation)
123Ah Not used 
Register
No.
Function name
Function
code
R/W Monitor and setting parameters
Resolu-
tion

Table of Contents

Other manuals for Omron 3G3RX