4-191
4-4 Communication Function
4
Functions
126Ah AVR voltage selection A082R/W
200-V class: 0 (200)
1 (215)
2 (220)
3 (230)
4 (240)
400-V class: 5 (380)
6 (400)
7 (415)
8 (440)
9 (460)
10 (480)
126Bh Not used 
126Ch Not used 
126Dh RUN mode selection A085R/W
00: Normal operation
01: Energy-saving operation
02: Automatic operation
126Eh
Energy-saving response/
accuracy adjustment
A086 R/W 0.0 to 100.0 0.1 [%]
126Fh
to
1273h
Not used 
1274h
Acceleration time 2
A092
(HIGH)
R/W
0.01 to 3600.00 0.01 [s]
1275h
A092
(LOW)
R/W
1276h
Deceleration time 2
A093
(HIGH)
R/W
0.01 to 3600.00 0.01 [s]
1277h
A093
(LOW)
R/W
1278h
2-step acceleration/
deceleration selection
A094 R/W
00: 2CH-Terminal (Switched via
multifunction input 09)
01: Preset FQ (Switched by setting)
02: FWD-REV (Enabled only when
switching forward/reverse)
1279h
2-step acceleration
frequency
A095
(HIGH)
R/W
0.00 to 400.00
0.01
[Hz]
127Ah
A095
(LOW)
R/W
127Bh
2-step deceleration
frequency
A096
(HIGH)
R/W
0.00 to 400.00
0.01
[Hz]
127Ch
A096
(LOW)
R/W
127Dh
Acceleration pattern
selection
A097 R/W
00: Line
01: S-curve
02: U-curve
03: inv.U curve
04: EL-S curve
127Eh
Deceleration pattern
selection
A098 R/W
00: Line
01: S-curve
02: U-curve
03: inv.U curve
04: EL-S curve
Register
No.
Function name
Function
code
R/W Monitor and setting parameters
Resolu-
tion

Table of Contents

Other manuals for Omron 3G3RX

Related product manuals