App-11
Appendix-1 Parameter List
Appendix
Upper/Lower limit, Jump
A063
Jump frequency 1
[Jump FQ1 Center]
Jump frequency: 0.0 to 400.0
Jump frequency width: 0.0 to 10.0
0.00
No Hz
4-30
A064
Jump frequency
width 1
[Jump FQ1 Width]
0.50
A065
Jump frequency 2
[Jump FQ2 Center]
0.00
A066
Jump frequency
width 2
[Jump FQ2 Width]
0.50
A067
Jump frequency 3
[Jump FQ3 Center]
0.00
A068
Jump frequency
width 3
[Jump FQ3 Width]
0.50
A069
Acceleration stop
frequency
[Accel hold FQ]
0.00 to 400.00 0.00 No Hz
A070
Acceleration stop
time
[Accel hold time]
0.0 to 60.0 0.0 No s
PID control
A071
PID selection
[PID enable]
00: OFF (Disabled)
01: ON (+) (Enabled)
02: ON (+/-) (Reverse output enabled)
00 No
4-31
A072
PID P gain
[PID P gain]
0.2 to 5.0 1.0 Yes
A073
PID I gain
[PID I gain]
0.0 to 3600.0 1.0 Yes s
A074
PID D gain
[PID D gain]
0.00 to 100.00 0.00 Yes s
A075
PID scale
[PID scale convert]
0.01 to 99.99 1.00 No Time
A076
PID feedback
selection
[PV source select]
00: OI
01: O
02: Modbus (RS485 communication)
03: Pulse (Pulse train frequency)
10: Math (Operation function output)
00 No
A077
Reverse PID function
[Reverse PID action]
00: OFF (Deviation = Target value -
Feedback value)
01: ON (Deviation = Feedback value - Target
value)
00 No
A078
PID output limit
function
[PID limit]
0.0 to 100.0 0.0 No %
A079
PID feedforward
selection
[PID F-Fwd select]
00: Disabled
01: O
02: OI
03: O2
00 No 4-31
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.