Appendix-1 Parameter List
Appendix
Momentary power interruption/Trip restart
b009
Undervoltage retry
time selection
[Under voltage retry]
00: 16 times
01: No limit
00 No
4-42
b010
Overvoltage/
overcurrent retry time
selection
[No. Of restart OV/
OC]
1 to 3 3 No Time
b011
Trip retry wait time
[Retry wait time OV/
OC]
0.3 to 100.0 1.0 No s
Electronic Thermal
b012
Electronic thermal
level
[E. Thermal Level]
0.20 × Rated current to 1.00 × Rated current
Rated
current
No A
4-46
b212
* 2nd electronic
thermal level
[E. Thermal Level-
M2]
b312
* 3rd electronic
thermal level
[E. Thermal Level-
M3]
b013
Electronic thermal
characteristics
selection
[E. Thermal
Character]
00: Reduced TRQ (Reduced torque
characteristics)
01: Const TRQ (Constant torque
characteristics)
02: Free set (Free setting)
00 No
b213
* 2nd electronic
thermal
characteristics
selection
[E. Thermal
Character-M2]
b313
* 3rd electronic
thermal
characteristics
selection
[E. Thermal
Character-M3]
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001