App-19
Appendix-1 Parameter List
Appendix
Lock
b031
Soft lock selection
[Softlock select]
00: Lock (SFT) (Data other than b031 cannot
be changed when terminal SFT is ON)
01: Only FQ (SFT) (Data other than b031 and
the specified frequency parameter cannot
be changed when terminal SFT is ON)
02: Lock (Data other than b031 cannot be
changed)
03: Only FQ (Data other than b031 and the
specified frequency parameter cannot be
changed)
10: RUN chg mode (Data other than
parameters changeable during operation
cannot be changed)
01 No 4-51
Others
b034
RUN time/Power ON
time setting
[RNT/ONT time]
0 to 65535 0 No h 4-52
b035
Rotation direction
limit selection
[Rotation restriction]
00: FREE (Forward and Reverse are
enabled)
01: FWD (Only Forward is enabled)
02: REV (Only Reverse is enabled)
00 No 4-52
b036
Reduced voltage
startup selection
[Reduced V start]
0 (Reduced voltage startup time: small) to
255 (Reduced voltage startup time: large)
6No 4-53
b037
Display selection
[Display restriction]
00: All (Complete display)
01: Utilized (Individual display of functions)
02: User (User setting)
03: Compare (Data comparison display)
04: Basic (Basic display)
00 No 4-53
b038
Initial screen
selection
[Initial display]
000 to 202 001 No 4-56
b039
User parameter
automatic setting
function selection
[Auto U param. regist]
00: OFF (Disabled)
01: ON (Enabled)
00 No 4-57
Torque limit
b040
Torque limit selection
[TRQ limit select]
00: 4-quadrant (Four-quadrant separate
setting)
01: TRQ input (Terminal switch)
02: [O] input (Analog input)
03: Option 1
04: Option 2
00 No -
4-57
4-59
b041
Torque limit 1
(Four-quadrant mode
forward power
running)
[TRQ limit FW/POW]
0 to 200 (0.4 to 55 kW)
0 to 180 (75 to 132 kW)
no (Torque limit disabled)
150 No %
4-57
4-59
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.