EasyManua.ls Logo

Omron 3G3RX - Page 416

Omron 3G3RX
452 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
App-21
Appendix-1 Parameter List
Appendix
Others
b050
Selection of non-stop
function at
momentary power
interruption
[Ctrld decel. select]
00: OFF (Disabled)
01: V-Cnst (STOP) (Enabled (deceleration
stop))
02: NS1 (Enabled (without recovery))
03: NS2 (Enabled (with recovery))
00 No
4-60
b051
Starting voltage of
non-stop function at
momentary power
interruption
[DC Volt ctrld. decel]
0.0 to 1000.0
220/
440
No V
b052
Stop deceleration
level of non-stop
function at
momentary power
interruption
[OV lvl ctrld. decel]
0.0 to 1000.0
360/
720
No V
b053
Deceleration time of
non-stop function at
momentary power
interruption
[Decel time ctrld. dec]
0.01 to 3600.00 1.00 No s
b054
Deceleration starting
width of non-stop
function at
momentary power
interruption
[FQ drop ctrld. decel]
0.00 to 10.00 0.00 No Hz
b055
Proportional gain
setting of non-stop
function at
momentary power
interruption
[P gain ctrld. decel]
0.00 to 2.55 0.20 Yes
b056
Integral time setting
of non-stop function
at momentary power
interruption
[I gain ctrld. decel]
0.000 to 65.535
0.100
Yes s 4-63
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.

Table of Contents

Other manuals for Omron 3G3RX

Related product manuals